Rosemount™ 965 Flame Detector
The Rosemount 965 uses Multi-Spectrum Infrared Flame Detection with QuadSense™ technology to accurately analyze the multi-spectral signals of hydrocarbon gas or liquid fires using four infrared (IR) sensors. Its ability to differentiate flame sources from non-flame background radiation offers high immunity to false alarms for fires up to 150 ft (45 m) from the device. Five selectable sensitivity levels help you customize settings for your specific application.
Features
Fast and reliable flame detection at up to 150 ft (45 m)
Proven false alarm immunity
Quick response time
Factory calibrated for life use
Five selectable sensitivity levels adapting to a variety of applications
Infrared built-in test (BIT) for continuous integrity verification of optics and electronics
HART communication
An internal log event recorder
Universal wiring option for a streamlined ordering process
Multiple output options for maximum compatibility with standard infrastructures
Two-year warranty with extended warranty option
Specifications
Spectral response: 4 infrared (IR) bands between 4 μm and 5 μm
Response Time: Detection: Typically < 5 seconds
Sensitivity Range: 3m, 10m, 20m, 30m, 45m
Field of view
Horizontal: 100° (at 50% of maximum distance)
Vertical: 95° (at 50% of maximum distance)
Temperature range: 40 to +158 °F (-40 to +70 °C)
Humidity Range: Non-condensing relative humidity up to 100%
Operating voltage: 24 Vdc nominal (12-32 Vdc)
Cable entries: 1 x M20
Input: Electrical input protection: According to EN 50130
Electromagnetic compatibility
Electromagnetic interference (EMI)/radio frequency interference (RFI) protected to EN61000-6-3, EN61000-6-4, EN61000-6-6, and EN 50130
Interface: Electrical: 9 terminals and a single cable conduit
Output
Relays:
Fault: Normally closed (NC)
Alarm: Normally open (NO)
SPST volt-free contacts rated 2 A at 30 Vdc
0-20 mA (stepped) default:
Fault: < 1.1 mA
Built-in test (BIT) fault: 2 mA ± 0.3 mA
Normal: 4 mA ± 0.3 mA
Warning: 16 mA ± 0.3 mA
Alarm: 20 mA ± 0.3 mA
HART® protocol:
HART communication on the 0-20mA analog current (FSK) used for maintenance, configuration changes, and asset management, available in mA source output wiring options.
RS-485:
RS-485 Modbus®-compatible communication link that can be used in computer-controlled installations